Generator Sizing Calculator
Estimate minimum generator wattage from running load, motor surge demand, and NEC continuous load rules — with safety warnings for large units and high inrush loads on 120 V and 240 V circuits.
Load Details
Live Results
Recommended Generator Size
4,500 W
Adjusted Running Watts
3,000 W
Running Watts
3,000 W
Surge Watts
4,500 W
Voltage
120 V
Continuous Load
No
Generator sizing follows NEC continuous load guidelines. Always verify final design with local electrical code and a licensed electrician.
How to Use This Generator Sizing Calculator
- Add up running watts. Enter the total running (rated) wattage of all equipment you plan to power simultaneously — use nameplate or manual values for refrigerators, sump pumps, HVAC, lighting, and critical circuits. Running watts represent steady-state power draw after motors and compressors have started.
- Enter surge (starting) watts. Input the highest combined starting surge for motor-driven loads — typically refrigerators, well pumps, air conditioners, and table saws. Surge watts are the brief inrush current at startup and often exceed running watts by 2× or more. The generator must support this peak even if it lasts only a few seconds.
- Select system voltage. Choose 120 V for standard branch-circuit backup or 240 V for whole-home panels, well pumps, and large appliances on double-pole circuits. Voltage is recorded for planning transfer switch and cord configuration — the watt-based sizing formula uses running and surge values directly.
- Mark continuous loads if applicable. Check Continuous Load when any backed-up equipment is expected to run for 3 hours or more — examples include refrigerators, freezers, medical equipment, and heat pumps. The NEC 125% rule increases adjusted running watts before comparing against surge demand.
- Review recommended size and warnings. The results panel shows recommended generator wattage as the greater of adjusted running watts and surge watts. Review large-generator and high-surge warnings, then confirm transfer switch rating, fuel capacity, and conductor sizing with the Breaker Size and Wire Gauge calculators.
Formulas & Example
Generator sizing compares adjusted running watts against peak surge demand and selects the larger value as the minimum recommended generator rating.
Adjusted Running Watts = Running Watts × (Continuous ? 1.25 : 1.00)
Recommended Generator (W) = max(Adjusted Running Watts, Surge Watts)Worked Example
3,000 W running, 4,500 W surge, 120 V, continuous load off:
Running Watts = 3,000 W
Surge Watts = 4,500 W
Voltage = 120 V
Continuous Load = No
Adjusted Running Watts = 3,000 × 1.00 = 3,000 W
Recommended Generator = max(3,000, 4,500) = 4,500 WSurge demand governs in this example because motor starting watts exceed steady running load. If continuous load were enabled, adjusted running would be 3,750 W (3,000 × 1.25) — still below surge, so 4,500 W remains the minimum. Pair this tool with the Breaker Size, Voltage Drop, Wire Gauge, and Conduit Fill calculators for complete backup power planning.
Frequently Asked Questions
What size generator do I need?▾
What are surge watts?▾
What is the NEC continuous load rule?▾
Does voltage affect generator sizing?▾
Should I oversize my generator?▾
Related Tools
Browse all Electrical calculators · Full directory