Wire Gauge (AWG) Calculator
Size copper or aluminum conductors from amperage, circuit length, and voltage ā with voltage drop checked against your allowable limit to recommend the minimum AWG gauge that meets both ampacity and drop requirements.
Circuit Details
Live Results
Recommended AWG Gauge
12 AWG
Voltage Drop
3.19 V
Voltage Drop
2.65%
Amperage
20A
Circuit Length
50ft
Conductor Material
Copper
Load too high for small-gauge conductors. Larger wire required.
This is an estimation tool based on standard NEC resistivity and ampacity values. Always consult local electrical codes and a licensed electrician for final design.
How to Use This Wire Gauge Calculator
- Enter the circuit amperage. Input the continuous load current in amperes ā use the breaker rating or the nameplate FLA for motors and appliances. For general branch circuits, common values are 15 A for lighting, 20 A for kitchen and bathroom receptacles, and 30 A for dryers or water heaters on dedicated circuits.
- Measure one-way circuit length. Enter the one-way distance in feet from the panel to the load, not the round-trip wire path. The calculator applies the standard factor of 2 for outbound and return conductors in the voltage drop formula.
- Select system voltage. Choose 120 V for standard single-pole branch circuits or 240 V for large appliances, HVAC equipment, and double-pole circuits. Higher voltage reduces the percentage voltage drop for the same wire size and current.
- Choose conductor material. Select copper for most branch circuits and short runs, or aluminum for larger feeders where cost savings matter. Aluminum requires proper terminations and is typically limited to 8 AWG and larger for branch-circuit work in many jurisdictions.
- Set allowable voltage drop. Use 3% as the default for branch circuits per common NEC guidance (5% total from service to load). Increase the slider only when local code or engineering practice allows a higher drop ā the recommended AWG updates instantly as you adjust inputs.
Formulas & Example
Voltage drop uses the standard single-phase formula with a factor of 2 for the outbound and return conductors. Resistivity is expressed in ohm-cmil per foot. The calculator scans AWG sizes from 14 through 4/0 and selects the smallest conductor that meets both ampacity and voltage drop limits.
Voltage Drop (V) = (2 Ć Circuit Length (ft) Ć Resistivity Ć Amperage) Ć· Circular Mil Area
Voltage Drop (%) = (Voltage Drop Ć· System Voltage) Ć 100
Resistivity (ohm-cmil/ft):
Copper: 10.4
Aluminum: 17.0
Required AWG = smallest gauge where:
Ampacity (material) ā„ Amperage
Voltage Drop % ⤠Max Allowable Drop %Worked Example
A 20 A load on a 50 ft one-way run at 120 V with copper conductors and a 3% maximum voltage drop:
14 AWG: ampacity 15 A < 20 A ā fails ampacity
12 AWG: ampacity 20 A ā„ 20 A ā
CMIL = 6,530
Voltage Drop = (2 Ć 50 Ć 10.4 Ć 20) Ć· 6,530 = 3.19 V
Voltage Drop % = (3.19 Ć· 120) Ć 100 = 2.66% ⤠3% ā
Recommended: 12 AWG copperIf the same circuit were 100 ft, 12 AWG would exceed 3% drop and the calculator would recommend 10 AWG. Always confirm ampacity tables, derating factors, and termination requirements against the current NEC and local amendments before pulling wire.
Frequently Asked Questions
What is AWG?ā¾
What are the differences between copper and aluminum wire?ā¾
What is an acceptable voltage drop?ā¾
How does circuit length affect wire size?ā¾
Can I use aluminum wire for branch circuits?ā¾
Related Tools
Explore more free calculators. Back to home