Voltage Drop Calculator
Calculate voltage drop in volts and percent for a given AWG conductor, amperage, circuit length, and system voltage — compare copper and aluminum runs before you pull wire or size a feeder.
Circuit Details
Live Results
Voltage Drop
3.19V
Voltage Drop
2.65%
Amperage
20A
Circuit Length
50ft
Voltage
120V
Wire Gauge
12 AWG
Conductor Material
Copper
Voltage drop calculations use standard NEC resistivity values. Always verify final wire sizing with local electrical code.
How to Use This Voltage Drop Calculator
- Enter the circuit amperage. Input the load current in amperes — use the breaker rating, nameplate FLA, or calculated load for the circuit. Common branch-circuit values are 15 A for lighting, 20 A for general receptacles, and 30 A or higher for dedicated appliance circuits.
- Measure one-way circuit length. Enter the one-way distance in feet from the panel to the load. The calculator applies the standard factor of 2 in the voltage drop formula to account for both outbound and return conductors in a single-phase circuit.
- Select system voltage. Choose 120 V for standard single-pole branch circuits or 240 V for large appliances, HVAC equipment, and double-pole circuits. The same absolute voltage drop in volts produces a lower percentage drop on 240 V systems.
- Choose conductor material. Select copper for most branch circuits and short runs, or aluminum for feeders and larger conductors where material cost matters. Aluminum has higher resistivity and produces more voltage drop for the same AWG size compared to copper.
- Select wire gauge. Pick the AWG size of the conductor you plan to use or want to evaluate. Results update instantly — compare voltage drop across gauges to see whether upsizing wire or shortening the run is needed to stay within recommended limits.
Formulas & Example
Voltage drop uses the standard single-phase formula with a factor of 2 for the outbound and return conductors. Resistivity is expressed in ohm-cmil per foot for copper and aluminum conductors.
Voltage Drop (V) = (2 × Circuit Length (ft) × Resistivity × Amperage) ÷ Circular Mil Area
Voltage Drop (%) = (Voltage Drop ÷ System Voltage) × 100
Resistivity (ohm-cmil/ft):
Copper: 10.4
Aluminum: 17.0Worked Example
A 20 A load on a 50 ft one-way run at 120 V with 12 AWG copper conductors:
CMIL (12 AWG) = 6,530
Resistivity (copper) = 10.4 ohm-cmil/ft
Voltage Drop = (2 × 50 × 10.4 × 20) ÷ 6,530 = 3.19 V
Voltage Drop % = (3.19 ÷ 120) × 100 = 2.66%
Result: 3.19 V drop (2.66%) — within the recommended 3% branch-circuit limitThe same circuit with 12 AWG aluminum would produce about 5.21 V (4.34%) because aluminum resistivity is higher. Upsizing to 10 AWG aluminum or using copper would bring drop back within recommended limits. Pair this tool with the Wire Gauge (AWG) Calculator to find the minimum gauge that satisfies both ampacity and drop requirements.
Frequently Asked Questions
What is voltage drop?â–¾
What is acceptable voltage drop?â–¾
Does wire gauge affect voltage drop?â–¾
What are the copper vs aluminum voltage drop differences?â–¾
How does circuit length affect voltage drop?â–¾
Related Tools
Explore more free calculators. Back to home