Breaker Size Calculator
Size circuit breakers from load amperage using NEC continuous load rules — apply the 125% multiplier for 3-hour loads and select the next standard breaker rating for 120 V and 240 V circuits.
Load Details
Live Results
Recommended Breaker Size
20A
Adjusted Load
20.00A
Load Amperage
20A
Voltage
120V
Continuous Load
No
Breaker sizing follows NEC 80% continuous load guidelines. Always verify final design with local electrical code and a licensed electrician.
How to Use This Breaker Size Calculator
- Enter the load amperage. Input the expected circuit current in amperes — use nameplate FLA for motors and appliances, or the calculated load for receptacle and lighting circuits. Common branch-circuit values are 15 A for lighting, 20 A for kitchen and bathroom receptacles, and 30 A or higher for dedicated appliance circuits.
- Select system voltage. Choose 120 V for standard single-pole branch circuits or 240 V for large appliances, HVAC equipment, and double-pole circuits. Voltage does not change the breaker ampere rating, but high loads on 120 V circuits may require larger conductors and panel capacity verification.
- Identify continuous vs non-continuous load. Check Continuous Load when the equipment is expected to run for 3 hours or more at full rated current — examples include water heaters, EV chargers, heat pumps, and commercial lighting. Non-continuous loads use 100% of the load current for breaker sizing.
- Review the adjusted load and recommended breaker. The calculator applies the NEC 125% rule for continuous loads to determine adjusted load amperage, then selects the smallest standard breaker size that meets or exceeds that value. Compare the result against wire gauge ampacity using the Wire Gauge Calculator.
- Verify warnings and local code. Review any high-load or large-breaker warnings before installation. Confirm conductor size, equipment ratings, and panel bus capacity with the current NEC edition and your local AHJ — this tool provides a planning estimate, not a final design.
Formulas & Example
Breaker sizing applies the NEC continuous load multiplier when the load runs 3 hours or more, then rounds up to the next standard breaker rating from the available size list.
Adjusted Load (A) = Load Amperage × (Continuous ? 1.25 : 1.00)
Recommended Breaker = smallest standard size ≥ Adjusted Load
Standard breaker sizes (A):
15, 20, 30, 40, 50, 60, 70, 80, 90, 100Worked Example
A 20 A non-continuous load on a 120 V circuit:
Load Amperage = 20 A
Continuous Load = No
Adjusted Load = 20 × 1.00 = 20 A
Standard sizes ≥ 20 A: 20, 30, 40 …
Recommended Breaker = 20 AIf the same 20 A load were continuous, adjusted load would be 25 A (20 × 1.25), requiring a 30 A breaker — the next standard size above 25 A. Pair this tool with the Wire Gauge (AWG) and Voltage Drop calculators to confirm conductor ampacity and circuit performance.
Frequently Asked Questions
What is the NEC 80% rule?â–¾
What is a continuous load?â–¾
Can I oversize a breaker?â–¾
Does voltage affect breaker size?â–¾
What breaker sizes are standard?â–¾
Related Tools
Explore more free calculators. Back to home