Three-Phase Power & Cost Estimator
Estimate three-phase real power, apparent power, reactive power, and daily, monthly, and yearly energy cost from voltage, current, and power factor — with service capacity PASS/FAIL checks.
Load Details
Live Results
Real Power
22.45kW
Apparent Power
24.94kVA
Reactive Power
10.87kVAR
Daily kWh
179.57
Monthly kWh
5,387.21
Yearly kWh
65,544.42
Daily Cost
$26.94
Monthly Cost
$808.08
Yearly Cost
$9,831.66
Service Capacity Check
Input Summary
Three-phase power calculations follow standard electrical engineering formulas. Always verify final design with local electrical code.
How to Use This Three-Phase Calculator
- Select system voltage. Choose the three-phase line-to-line voltage for your installation — 208 V for commercial wye systems, 240 V for delta or high-leg configurations, or 480 V for industrial and large commercial feeders. Voltage directly affects apparent power (kVA) and real power (kW) calculations.
- Enter load current. Input the measured or calculated line current in amperes from the motor nameplate, panel schedule, or clamp meter reading. Current represents the load drawn on each phase and is the primary driver of kVA and kW output.
- Set power factor. Enter the load power factor as a decimal between 0 and 1. Motors and inductive equipment typically run between 0.75 and 0.95 PF. Lower power factor increases reactive power (kVAR) and may trigger utility demand charges — use nameplate data when available.
- Enter operating hours and energy rate. Input daily run hours and your utility cost per kilowatt-hour ($/kWh) to estimate daily, monthly, and yearly energy consumption and operating cost. Monthly estimates use 30 days; yearly estimates use 365 days.
- Review power output, cost, and service capacity. Compare kVA, kW, and kVAR results against transformer and feeder ratings. Optionally enter selected service amperage to run a PASS/FAIL check — PASS means load current is within the selected service capacity. Review low power factor and high kVA warnings before finalizing design.
Formulas & Example
Three-phase power calculations convert line voltage and current into apparent, real, and reactive power, then project energy consumption and cost based on operating hours and utility rates.
Apparent Power (kVA) = (Voltage × Current × √3) ÷ 1000
Real Power (kW) = kVA × Power Factor
Reactive Power (kVAR) = kVA × √(1 − PF²)
Daily Energy (kWh) = kW × Hours Per Day
Monthly Energy (kWh) = Daily kWh × 30
Yearly Energy (kWh) = Daily kWh × 365
Daily Cost = Daily kWh × Cost Per kWh
Monthly Cost = Monthly kWh × Cost Per kWh
Yearly Cost = Yearly kWh × Cost Per kWh
Service PASS/FAIL = Current ≤ Selected Service AmpsWorked Example
A 480 V three-phase load drawing 30 A at 0.90 power factor:
Voltage = 480 V
Current = 30 A
Power Factor = 0.90
kVA = (480 × 30 × 1.732) ÷ 1000 ≈ 24.9 kVA
kW = 24.9 × 0.90 ≈ 22.4 kW
kVAR = 24.9 × √(1 − 0.90²) ≈ 10.9 kVARPair this tool with the Motor FLA Calculator, Transformer Sizing Calculator, Load Calculation Tool, Voltage Drop Calculator, and EV Charger Circuit & Load Calculator for complete three-phase system planning.
Frequently Asked Questions
What is three-phase power?â–¾
What is the difference between kW, kVA, and kVAR?â–¾
What affects energy cost?â–¾
What is power factor?â–¾
How do utilities bill three-phase loads?â–¾
Related Tools
- Motor FLA Calculator
- Transformer Sizing Calculator
- Load Calculation Tool
- EV Charger Circuit & Load Calculator
Explore more free calculators. Back to home