Gas Pipe Sizing Calculator (BTU Load + Equivalent Length)
Size low-pressure fuel gas branches from IFGC Table 402.4(1) — sum multi-appliance BTU loads, convert fittings to equivalent length, and pick the smallest black iron pipe that meets code capacity at 0.5 in. w.c. drop.
Gas System Inputs
Connected Appliances
Piping Layout
Live Results
Recommended Nominal Pipe Size
3/4" Black Iron Pipe
Total System Connected Load
100,000 BTU/hr
Total System Equivalent Length
60 ft
Flow Profile Compliant — Gas pipe diameter falls safely within National Fuel Gas Code safety envelopes. Volumetric fuel flow velocity guarantees perfect combustion.
Sizing uses IFGC Table 402.4(1) at 0.5 in. w.c. pressure drop for black iron pipe. Verify branch layout, meter capacity, and local fuel gas amendments before installation.
How to Use This Gas Pipe Sizing Calculator
- Select the gas type. Choose Natural Gas (NG) or Liquid Propane (LP). Propane has higher energy density per cubic foot, so LP capacities are scaled 1.60× above the natural gas IFGC Table 402.4(1) baseline for the same nominal pipe size and equivalent length.
- Enter connected appliance BTU loads. Add each gas appliance on the branch run with its input rating in BTU/hr — furnace, water heater, range, dryer, fireplace, or boiler nameplate values. Use Add Appliance for multiple connected loads; the calculator sums total demand automatically.
- Enter straight pipe length and fitting counts. Measure the developed straight run in feet, then count 90° elbows, 45° elbows, straight-run tees, and 90° branch tees. Each fitting adds equivalent length per IFGC practice: 90° = 5 ft, 45° = 3 ft, straight tee = 1 ft, branch tee = 5 ft.
- Review recommended nominal pipe size. Live Results show the smallest black iron pipe size whose table capacity meets total BTU demand at the computed equivalent length. Total connected load and equivalent length are displayed for field verification.
- Check the flow compliance badge. Green means safe margin under the code chart. Yellow warns when utilization exceeds 90% — consider upsizing if future appliances are likely. Red indicates demand exceeds 2" low-pressure chart capacity; split branches or move to a 2 PSI regulated system.
Formulas & Example
Branch sizing compares total connected appliance input against IFGC black iron capacity at the equivalent developed length. Propane uses the same natural gas chart multiplied by 1.60.
Equivalent Length (ft) =
Straight Pipe
+ (90° Elbows × 5)
+ (45° Elbows × 3)
+ (Tees Straight × 1)
+ (Tees Branch × 5)
Total BTU Load = Σ Appliance Input Ratings
LP Capacity = NG Table Value × 1.60
Select smallest nominal pipe where Table Capacity ≥ Total BTU LoadWorked Example
100,000 BTU/hr total load on natural gas, 40 ft straight run, 3 × 90° elbows, 1 × branch tee:
Equivalent Length = 40 + (3 × 5) + (1 × 5) = 60 ft → use 60 ft table column
3/4" at 60 ft = 137,000 BTU/hr ≥ 100,000 BTU/hr
Result: 3/4" Black Iron Pipe — ~73% utilization (compliant)If utilization exceeds 90% or demand exceeds 2" chart capacity, upsize the branch, split loops, or consult a 2 PSI regulated distribution design before final permit submission.
Frequently Asked Questions
What code table does this gas pipe sizing calculator use?▾
How is equivalent pipe length calculated?▾
Why is propane capacity higher than natural gas for the same pipe?▾
What if my gas load exceeds 2 inch pipe capacity?▾
Can I size a branch with multiple appliances on one run?▾