Refrigerant Charge Calculator (Superheat / Subcooling)
Diagnose R-410A refrigerant charge balance using superheat for fixed-orifice systems or subcooling for TXV metering. Live PT saturation lookups, dynamic target superheat, and phase cycle stability badges guide field charging decisions.
Refrigerant Charge Inputs
Target Evaluation Mode
Diagnostic Method
Superheat Structural Inputs
Live Results
Active Diagnostic Value
Calculated Superheat: 11.1°F
Metric Operational Profile Targets
System Design Target: 12.5°F
System Condition
SYSTEM CHARGE PROFILE: OVERCHARGED
Marginal Off-Target Shift — System charge exhibits a 10-20% slight operational variance. Performance efficiency will track low. Verify air filter clean state and coil cleanliness before adding mass.
R-410A Saturation Temp
38.9°F
PT Lookup Pressure
120 PSI
How to Use This Refrigerant Charge Calculator
- Select superheat or subcooling diagnostic mode. Choose Superheat Mode (Fixed Orifice) for piston or capillary-tube metering devices, or Subcooling Mode (TXV Valve) for thermostatic expansion valve systems. The input fields transition smoothly based on your selection.
- Enter gauge pressures and line temperatures. For superheat, input low-side suction pressure (100–200 PSI), suction line thermistor temperature, indoor wet bulb, and outdoor dry bulb. For subcooling, input high-side liquid pressure (250–500 PSI), liquid line temperature, and manufacturer target subcooling.
- Review calculated superheat or subcooling. The Live Results panel displays the calculated diagnostic value at 1-decimal precision using the R-410A PT lookup table. Saturation temperature is resolved from the closest indexed pressure key.
- Compare against system design target. Superheat target is dynamically calculated from outdoor dry bulb and indoor wet bulb conditions. Subcooling target uses the manufacturer frame value (default 12°F). Deviation and charge status are derived from measured vs. target comparison.
- Evaluate charge status and severity badge. Review the SYSTEM CHARGE PROFILE (UNDERCHARGED or OVERCHARGED) and the RED/YELLOW/GREEN phase cycle stability badge indicating whether deviation exceeds 10% or 20% of the design target.
Formulas & Example
Superheat and subcooling diagnostics compare measured line temperatures against R-410A saturation temperatures from the PT lookup index. Charge status and severity badges derive from deviation against design targets.
PT Lookup: satTemp = pt410a[closestPressureKey] || 40.0
Superheat Mode:
Calculated Superheat = Suction Line Temp − satTemp (at suction pressure)
Target Superheat = 5 + (Outdoor Dry Bulb − 70) × 0.1 + (Indoor Wet Bulb − 50) × 0.5
Deviation = Calculated − Target
Charge Status: Calculated > Target → UNDERCHARGED, else OVERCHARGED
Subcooling Mode:
Calculated Subcooling = satTemp (at liquid pressure) − Liquid Line Temp
Target Subcooling = Manufacturer Input (default 12.0°F)
Deviation = Calculated − Target
Charge Status: Calculated < Target → UNDERCHARGED, else OVERCHARGED
Severity:
percentError = |deviation| ÷ target
RED (>20%) | YELLOW (10–20%) | GREEN (≤10%)Worked Example — Superheat Mode
Suction pressure 120 PSI, suction line 50°F, outdoor 85°F dry bulb, indoor 62°F wet bulb:
PT Lookup: 120 PSI → satTemp = 38.9°F
Calculated Superheat = 50.0 − 38.9 = 11.1°F
Target Superheat = 5 + (85 − 70) × 0.1 + (62 − 50) × 0.5 = 12.5°F
Deviation = 11.1 − 12.5 = −1.4°F
Charge Status: 11.1 ≤ 12.5 → OVERCHARGED
percentError = 1.4 ÷ 12.5 = 11.2% → YELLOW badgeWorked Example — Subcooling Mode
Liquid pressure 325 PSI, liquid line 90°F, target subcooling 12°F:
PT Lookup: 325 PSI → satTemp = 102.1°F
Calculated Subcooling = 102.1 − 90.0 = 12.1°F
Target Subcooling = 12.0°F
Deviation = 12.1 − 12.0 = +0.1°F
Charge Status: 12.1 ≥ 12.0 → OVERCHARGED (within tolerance)
percentError = 0.1 ÷ 12.0 = 0.8% → GREEN badgeFrequently Asked Questions
What is superheat and when should I use it?▾
What is subcooling and when should I use it?▾
How does the R-410A PT lookup table work?▾
How is the dynamic superheat target calculated?▾
What do the RED, YELLOW, and GREEN severity badges mean?▾
Related Tools